Fire-Link FL-8

The regulations governing fire-fighting systems foresee the need for a transmission system that can transfer fire, fault and out-of-service alarms to an alarm receiving centre in the event of a 24-hour failure, so that the personnel in charge can promptly follow up on intervention measures.

The connection between the fire alarm system and the receiving stations must be constantly monitored and entrusted to an EN 54-21 compliant transmitter with dual communication vector, such as Fire-Link.

All unmanned sites that are required to have a fire detection system must therefore have such a connection. With their own monitoring centres and the supervised connection of the Fire-Link, security companies can take over and manage these reports, guaranteeing maximum operational security.

  • Bi-directional transmitter EN 54-21
  • Communication in: Lan, 4G/LTE, Sms and voice messages (TTS)
  • 8 inputs
  • 8 remote control outputs
  • PSTN input for SIA and Contact-ID conversion
  • MVS and SIA-IP DC09 protocol
  • Encrypted transmission of information
  • Adjustable transmission times (minimum polling time 90s)
  • ALWAYS-ON connection (roaming SIM compatibility)
  • Integrated anti-jamming system
  • UF-L connector for external antenna
  • Event history (max. 1024)
  • Status LEDs for system controls and communication
  • Integrated power supply and rechargeable backup battery
  • Local or remote programming
  • Full compatibility with MvsNET system, EN 50518 compliant
  • Reduced footprint
  •  Certifications
    • EN 54-21:2006 (CPR)
    • EN 50131-10:2015
    • EN 50136-1:2019
    • EN 50136-2:2014

TECHNICAL SPECIFICATIONS
DEPLIANT
DOWNLOADS
SOFTWARE
CERTIFICATIONS

TECHNICAL SPECIFICATIONS

Power supply Grid: 85-305Vac /120-430Vdc (Internal power supply); DC: 9-14Vdc
Absorption Max 40 mA @230Vac ; Max 70 mA @115Vac ; Max 500mA@12Vdc
Backup battery Rechargeable LiFePO4 battery pack 6.4Vcc 1500 mAh
Input channels 8, impedance 100 kΩ, Pull-up 100 kΩ on 3.3V
Remote control outputs 8, open collector on GND, 200mA max; static or monostable
Controlli Tamper anti-opening and anti-removal, Lan connection, Gsm signal, jamming on Gsm
Transmission protocols SIA-IP DC 09 ; NETP/TLS
Interfaces LAN Ethernet, GSM/LTE, PSTN line, USB Type B
Event history 1024 eventi
PSTN interface Line simulator for routing PSTN combiners to other carriers
Lan interface RJ45 Ethernet IEEE 802.3 10/100 LANport
4G / LTE module Built-in antenna + UF-L connector for external antenna; SMS sending; Data connection, speech synthesis.
Frequencies: E-GSM-900, DCS-1800, LTE-FDD B1, B3, B5, B7, B8, B20
LED signalling Network Presence, Battery Failure, Communications Failure, Message Acknowledgement
System Programming and Updating SicepConnect PC software, locally or remotely
Container protection cAnti-opening and Anti-removal
Dimensions 175 x 175 x 40 mm (L x H x P)
Weight 500g with battery pack
Certifications EN 54-21 (CPR)
EN50131-1
EN 50136-1 / EN 50136-2 Cat. DP4